UPS calculator: calculate UPS size in VA and runtime
Use the UPS calculator to find the right UPS size in VA from watts, cos φ, and headroom, or calculate runtime from battery data. See the calculation steps for each. Free, with no sign-up, right in your browser. For example, 450 W at cos φ 0.9 with 25 % headroom gives 650 VA.
Built by Luca Stanek
- VA and runtime
- Step-by-step calculation
- UPS types explained
- No sign-in required
Don't want to deal with batteries and power outages at home? A VPS runs in a data center, and we take care of the power and hardware.
Devices connected to the UPS
Add device
Power factor and headroom
Check the data sheet; exercises often use 0.6 to 0.9.
Headroom for startup currents.
Result
Recommended UPS size
650 VA
Common UPS sizes
600 VA
too small
650 VA
matches
750 VA
more reserve
- Active power
- 450 W
- Apparent power
- 500 VA
- With reserve
- 625 VA
- Watts with reserve
- 562.5 W
A 450 W load at cos φ 0.9 requires 625 VA with 25% reserve, so you need a 650 VA UPS.
Calculation steps (4)
- 1Real power P: 400 W + 50 W = 450 W
- 2Apparent power S = P ÷ cos φ = 450 W ÷ 0.9 = 500 VA
- 3With 25% reserve: 500 VA × 1.25 = 625 VA
- 4Next standard UPS size: 650 VA
Simplified estimate. For purchasing decisions, refer to the runtime curve in the datasheet.
Why this calculator
Plan your UPS without guesswork
UPS size, runtime, and battery capacity in one calculator—for homelabs, office IT, and exam questions.
UPS size in VA
Calculate apparent power from watts and cos φ, with headroom and the next standard UPS size from 400 to 20,000 VA, regardless of manufacturer.
Runtime
How many minutes the batteries can support your load, based on capacity, voltage, number of batteries, and efficiency.
Battery capacity for your desired runtime
How many Wh and Ah you need for a target time in minutes.
Multiple devices with quantities
Enter each server, PC, router, or switch separately; the calculator adds up their active power.
Step-by-step calculation
Every step shown with your numbers, so you can check the math or use it for exam questions.
Free, no sign-up required
Runs right in your browser; your values only appear in the URL for sharing.
How it works
How to calculate your UPS requirements
Free, with no account, right in your browser.
Step 1
Choose calculation
Choose whether to calculate UPS size in VA or battery runtime.
Step 2
Enter devices
Enter each device's active power in watts and the quantity; the calculator adds up the load.
Step 3
Size: cos φ and headroom
For UPS sizing, choose the power factor cos φ (0.6 to 1) and headroom (0, 20, 25, or 30 %), or enter your own values.
Step 4
Runtime: battery data
For runtime, enter capacity in Ah, voltage (12, 24, 36, or 48 V), number of batteries, and efficiency. You can also enter a target time in minutes.
Step 5
Read result
See the recommended UPS size or runtime in minutes, with step-by-step calculations.
Step 6
Share calculation
Copy the result with its calculation steps or share a link containing your values.
Formulas
How to size a UPS
The formulas from the first part of the IT specialist exam, each with an example.
Apparent power
S (VA) = P (W) ÷ cos φ
450 W ÷ 0,9 = 500 VA
Headroom
S with headroom = S × (1 + headroom)
500 VA × 1,25 = 625 VA, so a 650 VA UPS
Battery energy
Wh = Ah × V × quantity
9 Ah × 12 V × 2 = 216 Wh
Runtime
t (h) = Wh × efficiency ÷ P
216 Wh × 0,9 ÷ 450 W = 25.9 min
Batteries in series or parallel
Series: voltages add up; parallel: Ah values add up
2 × 12 V/9 Ah: in series 24 V/9 Ah, in parallel 12 V/18 Ah; both provide 216 Wh
UPS classes according to IEC 62040-3
VFD (Offline), VI (Line-Interactive), VFI (Online)
VFD switches over during an outage, VI also regulates voltage, and VFI continuously supplies power through the inverter
Discover more
More tools
Subnet Calculator
Calculate the network address, broadcast address, subnet mask, and usable host range from a CIDR address, and convert between CIDR and IP ranges (IPv4 and IPv6).
Built by Jakub Martyniak
RAID Calculator
Calculate usable capacity, overhead, and fault tolerance for RAID 0, 1, 5, 6, 10, 50, 60, and JBOD, including hot spares and warnings for invalid drive combinations.
Built by Eric Mager
Uptime & SLA Calculator
NewConvert uptime percentages into allowed downtime per day, week, month, quarter, and year, or calculate uptime from measured downtime, for SLA targets from 99% to 99.999%.
Built by Luca Stanek
PSU Calculator (Power Supply Calculator)
Power supply calculator for your PC: Choose a CPU and GPU class or wattage, configure accessories and overclocking, and see the recommended power supply wattage with headroom.
Built by Dimitri Heissler
Electricity Cost Calculator
NewCalculate electricity costs for PCs, servers, NAS devices and network equipment: enter watts, hours and electricity price, then view kWh and costs per day, month and year with calculations.
Built by Luca Stanek
Storage Calculator
NewCalculate storage needs for images, audio and video: enter resolution, color depth, sample rate or bitrate, and view the size in bytes, KiB, MiB and GiB with calculations for AP1.
Built by Luca Stanek
FAQ
Frequently asked questions
Quick answers about UPS size, VA and watts, and runtime.
The required apparent power in VA with a safety margin and the next standard UPS size, or the backup runtime from the battery data, each with calculation steps. Example: A 450 W load at cos φ 0.9 requires 625 VA with 25% reserve, so you need a 650 VA UPS.
Total active power of all devices in watts ÷ cos φ = apparent power in VA. Usually, you then add 20 to 30 % headroom. The calculator rounds up to the next standard UPS size between 400 and 20,000 VA: 450 W at cos φ 0.9 with 25 % headroom gives 625 VA, so you need a 650 VA UPS. The UPS must support both the VA rating and the wattage; both are listed in its datasheet.
Watts measure the active power a device uses; VA measure the apparent power the UPS must supply. P = S × cos φ, or S = P ÷ cos φ: a 1000 VA UPS delivers at most 600 W at cos φ 0.6, or 900 W at cos φ 0.9.
Use the value from the datasheet or your exercise. Modern server power supplies range from 0.9 to 0.99; older devices and many exam questions use 0.6 to 0.8. In the calculator, click to choose 0.6, 0.7, 0.8, 0.9, or 1, or enter your own value. The default is 0.9.
Runtime, also called backup time: Ah × V × number of batteries gives the watt-hours. Multiply by efficiency for usable energy, divide by the load in watts for hours, then multiply by 60 for minutes. Two 12 V, 9 Ah batteries last about 26 minutes at 90 % efficiency with a 450 W load.
The VA rating alone doesn't tell you. It only limits the power output; runtime depends on the batteries (Ah, voltage, and number) and the actual load. Enter both in Runtime mode to calculate the minutes.
In Runtime mode, enter a target time in minutes. The calculator then shows the energy needed in Wh (load × minutes ÷ 60 ÷ efficiency) and the capacity in Ah, calculated by dividing by the total voltage of the batteries in series.
The calculation is linear and does not account for the Peukert effect, aging, or minimum battery voltage. Lead-acid batteries deliver less than their rated capacity at high loads and lose performance in the cold. For planning, use the runtime curve in the datasheet.
The IEC 62040-3 standard defines three classes: VFD (offline) switches over only during a power outage, VI (line-interactive) also compensates for voltage fluctuations, and VFI (online) continuously supplies devices through the inverter.
No. The calculator runs in your browser without sign-up. Your values only appear in the URL so you can share the calculation by link.
Any more questions?
Contact SupportYour server in a data center instead of relying on your own battery
The data center handles power and hardware: root access, a static IP and fast connectivity included.
No setup. No risk. Online in seconds.
Looking for more tools? View all calculators & converters